Benefits
Versatility
The special matching of the flame geometry to the heat generator 's combustion chamber is every Weishaupt burner's recipe for success. The combination of electronic compound regulation and the right mixing assembly
allows customised use on different heat generators thermal process plant.
Also suitable for biogenic fuels
Weishaupt oil and dual-fuel burners are generally suitable for gas oil and low-sulphur gas oil (#2 oil as per ASTM D396). Bio-oil blends up to B10 can also be used in the same way as standard oils without any need for concern – guaranteed
Applications
Futureproof
The digital combustion management system employed by monarch® burners offers the possibility of communication with other systems, enabling the burner to be integrated with building management and other automation systems. Industry standards, like remote control, monitoring, and fault diagnosis, are well understood by Weishaupt.
Technology
multiflam®
Weishaupt's patented multiflam® technology enables large combustion plant to meet very low emission limits.
Key to the system is a special mixing assembly that establishes an internal flue gas recirculation. This cools the flame and reduces the formation of nitrogen oxides. The NOx levels that can be achieved are comparable to those of compact burners.
The various Weishaupt burners that are available in multiflam® execution cover a range of capacities extending from 340 to 78,500 MBTU/h.
Flue gas recirculation
Weishaupt's 4LN-version burners meet the world's most stringent emissions limits. A 4LN-version burner is equipped with a flue gas recirculation system that has its control components integrated into the burner.
Gaseous fuels contain almost no sulphur, and so their flue gases mostly comprise carbon dioxide
(CO
2), steam (H2O), and nitrogen (N2). This is beneficial to the flue gas recirculation, since there is no ash or soot to contaminate the system.
Special adaptations of the mixing assembly together with the W-FM200 digital combustion manager
ensure a high degree of flame stability and reliable operational behaviour.
Premix
NOx emission values below 10 ppm are achieved by Weishaupt premix burners.
Premixing followed by surface-stabilised combustion has been state of the art for many years in small condensing boilers. Premix Low-NOx (PLN) burners with NOxemissions below 10 ppm are the result of further development work at Weishaupt to extend premix technology to burners with larger capacity ranges.
Surface-stabilised combustion relies on a homogeneous gas/air mixture. For that reason, a totally new mixing assembly was developed for the PLN-version burners. A key feature is the separated gas and air feeds, with the two media not being brought together before the burner tube.
WM-series monarch® burners
| Type | Rating (MBTU/h) | |
|---|---|---|
| WM-G10/2 | 290 - 2,388 |
|
| WM-G10/3 | 444 - 3,583 |
|
| WM-G10/4 | 444 - 3,924 |
|
| WM-G20/2 | 614 - 5,801 |
|
| WM-G20/3 | 853 - 8,530 |
|
| WM-G20/4 | 1,024 - 10,236 |
|
| WM-G30/2 | 1,877 - 17,061 |
|
| Type | Rating (MBTU/h) | |
|---|---|---|
| WM-G20/2 | 682 - 4,948 |
|
| WM-G20/3 | 1,194 - 6,824 |
|
| WM-G30/1 | 1,365 - 12,966 |
|
| WM-G30/2 | 1,706 - 17,061 |
|
| WM-G30/3 | 1,706 - 17,061 |
|
| WM-G50/1 | 3,412 - 25,591 |
|
| WM-G50/2 | 3,412 - 37,534 |
|
| Type | Rating (MBTU/h) | |
|---|---|---|
| WM-G10/2 | 341 - 2,047 |
|
| WM-G10/3 | 427 - 3,071 |
|
| WM-G20/2 | 682 - 4,948 |
|
| WM-G20/3 | 1,194 - 6,824 |
|
| WM-G30/1 | 1,365 - 11,942 |
|
| WM-G30/2 | 1,706 - 15,355 |
|
| WM-G30/3 | 1,706 - 17,061 |
|
| Type | Rating (MBTU/h) | |
|---|---|---|
| WM-G10/1 | 188 - 1,194 |
|
| WM-G10/2 | 256 - 2,150 |
|
| WM-G10/3 | 427 - 3,071 |
|
| WM-G10/4 | 427 - 3,753 |
|
| WM-G20/2 | 853 - 5,459 |
|
| WM-G20/3 | 1,024 - 6,824 |
|
| WM-G30/1 | 1,194 - 9,554 |
|
| WM-G30/2 | 1,365 - 12,966 |
|
| WM-G30/3 | 2,047 - 18,426 |
|
| WM-G30/4 | 2,730 - 20,473 |
|
| Type | Rating (MBTU/h) | |
|---|---|---|
| WM-G10/1 | 188 - 1,382 |
|
| WM-G10/2 | 222 - 2,150 |
|
| WM-G10/3 | 341 - 3,412 |
|
| WM-G10/4 | 375 - 4,265 |
|
| WM-G20/2 | 512 - 7,165 |
|
| WM-G20/3 | 1,194 - 8,872 |
|
| WM-G30/1 | 1,194 - 10,578 |
|
| WM-G30/2 | 1,535 - 13,990 |
|
| WM-G30/3 | 2,047 - 19,449 |
|
| WM-G30/4 | 2,047 - 21,155 |
|
| WM-G50/1 | 2,730 - 27,297 |
|
| WM-G50/2 | 3,412 - 37,534 |
|
| WM-G50/3 | 3,412 - 40,946 |
|
| Type | Rating (MBTU/h) | |
|---|---|---|
| WM-G10/1 | 68 - 1,382 |
|
| WM-G10/2 | 102 - 2,150 |
|
| WM-G10/3 | 171 - 3,412 |
|
| WM-G10/4 | 205 - 4,265 |
|
| WM-G20/2 | 273 - 6,824 |
|
| Type | Rating (MBTU/h) | |
|---|---|---|
| WM-L10/2 | 409 - 2,047 |
|
| WM-L10/3 | 682 - 3,071 |
|
| WM-L20/2 | 1,365 - 4,948 |
|
| WM-L20/3 | 1,535 - 6,824 |
|
| WM-L20/4 | 1,194 - 8,360 |
|
| WM-L30/1 | 1,535 - 11,942 |
|
| WM-L30/2 | 2,047 - 15,355 |
|
| WM-L30/3 | 2,047 - 17,061 |
|
| Type | Rating (MBTU/h) | |
|---|---|---|
| WM-L10/1 | 256 - 1,382 |
|
| WM-L10/2 | 512 - 2,047 |
|
| WM-L10/3 | 853 - 2,730 |
|
| WM-L10/4 | 1,109 - 3,822 |
|
| WM-L20/1 | 1,365 - 4,777 |
|
| WM-L20/2 | 2,047 - 7,165 |
|
| WM-L20/3 | 2,730 - 8,872 |
|
| WM-L30/1 | 2,730 - 10,578 |
|
| WM-L30/2 | 3,071 - 13,990 |
|
| WM-L30/3 | 3,753 - 19,449 |
|
| WM-L50/1 | 4,095 - 27,297 |
|
| WM-L50/2 | 5,971 - 37,534 |
|
| WM-L50/3 | 5,971 - 40,946 |
|
| Type | Rating (MBTU/h) | |
|---|---|---|
| WM-S10/1 | 341 - 1,535 |
|
| WM-S10/2 | 597 - 2,388 |
|
| WM-S10/3 | 785 - 3,003 |
|
| WM-S10/4 | 1,024 - 3,822 |
|
| WM-S20/2 | 1,535 - 7,507 |
|
| WM-S20/3 | 2,388 - 8,360 |
|
| WM-S30/1 | 2,559 - 9,554 |
|
| WM-S30/2 | 3,071 - 12,625 |
|
| WM-S30/3 | 3,753 - 18,426 |
|
| Type | Rating (MBTU/h) | |
|---|---|---|
| WM-GL20/2 | 682 - 4,948 |
|
| WM-GL20/3 | 1,194 - 6,824 |
|
| WM-GL30/1 | 1,535 - 12,625 |
|
| WM-GL30/2 | 1,706 - 15,355 |
|
| WM-GL30/3 | 1,706 - 17,061 |
|
| WM-GL50/0 | 3,412 - 25,591 |
|
| WM-GL50/1 | 3,412 - 28,321 |
|
| WM-GL50/2 | 3,753 - 37,534 |
|
| Type | Rating (MBTU/h) | |
|---|---|---|
| WM-GL10/2 | 341 - 2,047 |
|
| WM-GL10/3 | 682 - 3,003 |
|
| WM-GL20/2 | 682 - 4,948 |
|
| WM-GL20/3 | 1,194 - 6,824 |
|
| WM-GL20/4 | 1,024 - 8,360 |
|
| WM-GL30/1 | 1,365 - 11,942 |
|
| WM-GL30/2 | 1,706 - 15,355 |
|
| WM-GL30/3 | 1,706 - 17,061 |
|
| Type | Rating (MBTU/h) | |
|---|---|---|
| WM-GL10/1 | 409 - 1,382 |
|
| WM-GL10/2 | 580 - 2,150 |
|
| WM-GL10/3 | 819 - 3,412 |
|
| WM-GL10/4 | 1,024 - 4,265 |
|
| WM-GL20/2 | 512 - 6,824 |
|
| WM-GL20/3 | 853 - 8,360 |
|
| WM-GL30/1 | 1,194 - 10,578 |
|
| WM-GL30/2 | 1,535 - 13,990 |
|
| WM-GL30/3 | 2,047 - 19,449 |
|
| WM-GL50/1 | 2,730 - 27,297 |
|
| WM-GL50/2 | 3,412 - 37,534 |
|
| WM-GL50/3 | 3,412 - 40,946 |
|
| Type | Rating (MBTU/h) | |
|---|---|---|
| WM-GS20/2 | 1,535 - 5,801 |
|
| WM-GS20/3 | 2,388 - 7,507 |
|
| WM-GS30/1 | 1,194 - 10,578 |
|
| WM-GS30/2 | 3,071 - 13,649 |
|
| WM-GS30/3 | 2,047 - 19,449 |
|